- Piece/Pieces
- 1
- Piece/Pieces
- 45000.00 - 98000.00 INR
- Siemen grey
- 24 V DC Volt-Ampere-Reactive (var)
- 125x125x71 Millimeter (mm)
- LM 6
- 1.5 Kilograms (kg)
- Fixed
- 60 Celsius (oC)
- 12 months
- User selectable
- Plant Safety
The Unit incorporates an extremely sensitive sensing circuit that responds to high energy sources in a bandwidth of 185 260 nm with optimum spectral sensitivity centred around 200 nm.
- Sensitive to virtually all fires including
Hydrogen and Hydrocarbon - Relay Output
- MODBUS (Optional)
- Virtually immune to:
1. Direct & reflected sunlight
2. Artificial Light source - Self-diagnosis including sensor check
- Ex-Proof
Specification
Technology | UV IR |
Model no. | UV-IR 250 |
Response time | < 3 seconds |
Adjustable Time Delay | 3 or 6 seconds |
Cone of vision | 120 minimum |
Optical Self-Test | Automatic continuous optical path |
Input Power | 20-35 VDC, 125 mA standby, 230 mA alarm @ 24 VDC |
Relay Contact Ratings | 2 amps @ 28 VDC or 300 VAC resistive |
Alarm Reset | Automatic or manual when the flame is no longer detected |
Communication | Available with optional MODBUS (RS-485) facility / HART |
Operating Temperature | -40F to 185F (-40C to 85C) |
Dimensions | 125 X 125 X 71 mm |
Weight | Approx. 350 grams (Weather Proof) / Approx. 2 kg (Ex-Proof) |
Compliance | EN 54-10, CCOE, SIL2, FM, ATEX, Vibration test |
- Telegraphic Transfer (T/T)
- 10 Per Month
- 4 Week
- Asia Middle East Africa
- All India
- CE